It is described by reference to the apparatus shown in Figures 9a and 9b, the circled numbers refer to those figures. When a bottle is used as a container Figure 9c , the mass of oil degassed is determined by weighing the degassing flask before and after introducing the oil. Get to Know Us. Therefore, the exact amount of oil introduced in a vial should be measured by weighing the vial or the syringe before and after introduction of the oil see 7. NOTE The actual density of oil measured according to ISO 1 or other standardized method should be used for the calibration procedure with gas-in-oil standards. This may need important modifications for some head-space samplers that have only mechanical reading of the pressure. This method will provide reproducible results only if all the operation and calibration parameters are precisely controlled, otherwise significant errors may occur. iec 60567

Uploader: Dolabar
Date Added: 6 April 2007
File Size: 37.68 Mb
Operating Systems: Windows NT/2000/XP/2003/2003/7/8/10 MacOS 10/X
Downloads: 27929
Price: Free* [*Free Regsitration Required]





A septum is attached to one side of the lid, and a vial crimper on the other side, both facing the mouth of the vials. See all free Kindle reading apps. Then close valve V9.

IEC | IEC Webstore

Weigh the oil-filled vial and subtract the weigh of the empty vial to get the mass of oil in the vial. Use the extraction procedure as detailed in 7.

Repeat the same procedure for the other nine samples. Again adjust the mercury levelling vessel to bring both the mercury surfaces to the new level and close valve.

The Toepler pump extraction apparatus shall a be capable of subjecting the liquid to a vacuum less than 10 Pa; b be vacuum-tight. The concentrations of the mixtures should be chosen in order to fully cover the expected concentration range of field samples, which depends on the type of equipment to be monitored. When an oil sample is run under exactly the same operational conditions, the concentration of the gases in the gas phase C G can be obtained by using this calibration curve.

Condition 10 to 20 vials from the same batch and ml of distilled water for 1 h at room temperature and note the temperature. Place a piece of paraffin film Parafilm R on the mouth of a vial. Read more Read less.

The highest accuracy on the K value is obtained when the correlation coefficient R of the regression is greater than 0, Alternatively, after the equipment has been evacuated, oil may be withdrawn from an oil sample bottle via a tube attached to valve V8 which has previously been filled with oil see Figure 9c. If the stripper is to be disconnected for cleaning, the gas outlet tube should be disconnected first to avoid the possibility of the oil sample entering the gas sampling valve.

Draw 15 ml of oil from the syringe then reweigh the syringe. The time required to extract larger volumes would give unacceptable gas chromatograms except when used with cold traps or for hydrogen analysis only.

Note that Figure 9b includes recommended volumes. This septum can be used several times 3 to 10 depending on the size of the needles before leakage occurs. Oil is injected into the stripper from a syringe via a rubber septum. Continue with steps fg and h as if oil were present. For procedure of 7. Their actual volume is closer to 22,3 ml.

Standards Catalogue

Partition coefficient K 60576 each compound is determined using modified equation 2 see 7. From the regression analysis of these data, obtain the slope and intercept.

To get the free app, enter mobile phone number. Release the 5 ml oil to waste and fill the glass syringe with 20 ml of oil. The same procedures apply to gas-in-oil standards.

iec 60567

NOTE 2 The minimum oil volume to be used is the volume necessary to produce enough gas volume for injection in the gas chromatograph. An electric counter is helpful in counting the number of cycles and for stopping the procedure after the required number of cycles, as established as standard for the apparatus.

iec 60567

For more accurate analyses, the partition coefficients of the oil analysed should be measured. The advantage of this method is that there is no requirement to prepare gas-in-oil standards for direct calibration of the headspace extractor. 06567 that the lined side is turned towards the inside of the vial and that the latter is properly sealed by trying to turn 6067 cap. Would you like to tell us about a lower price? The first quantity of extracted gas is retained in the burette by keeping valve V4 closed until the remainder of the system is re-evacuated step d above.